Coops 10053 error on Master PC only with erroneous persistent route not set failure

PROBLEM

 

Operator gets a COOPS 10053 controller network error when trying to open a station configuration on the master PC but not on a client PC using the same station configuration (Figure 1).  Moreover, the Test PC configuration Utility says the persistent route is not set even though the controller has only one processor and doesn’t require the persistent route to be set (Figure 2).  

 

Figure 1 – COOPS 10053 error

 

Figure 2 – Erroneous Persistent Route Not Set failure

 


 

ANSWER


 

Case Study

 

This problem was caused by cloud based anti-virus software that was operating over the company network.  By disconnecting from the company network the problem stopped.  